Sự cố vận hành và biện pháp khắc phục của thiết bị lạnh trong mùa đông

Operation problems and Countermeasures of refrigeration equipment in winter

In Winter, when the outdoor temperature is wet and low, and the condensation pressure has a great influence on the performance of the refrigeration system.

When the condensation pressure (or condensation temperature) is high, the compression ratio increases.

photo-1543896870-78e77bd02034

And the volumetric efficiency of the compressor decreases, resulting in the reduction of refrigeration capacity and the increase of power consumption. The higher the exhaust temperature and the higher the condensation pressure, the greater the adverse effect.

The phenomenon of high condensation pressure mainly occurs in Summer. At this time, the condensation pressure should be reduced as much as possible to ensure the economy and reliability of the system operation.

However, in winter, the condensation pressure of refrigeration equipment may be too low.

When the condensing pressure is too low, the pressure difference between the front and back of the expansion valve is too small, and the capacity of the expansion valve is reduced, resulting in the insufficient liquid supply capacity of the system refrigerant, the lack of liquid in the evaporator, and the refrigeration capacity of the system is greatly reduced, and the unit is protected under low pressure. Therefore, it is necessary to control the condensing pressure in a reasonable range, otherwise the refrigeration device will have frequent low-pressure alarm or low suction pressure alarm.

In order to avoid the winter operation risk of the cooling water system, we can start from :the cooling tower equipment, cooling tower operation strategy and the end pipeline setting.

To avoid the winter operation risk through the equipment side anti freezing, cooling tower start-up and shutdown and pipeline optimization design.

1.There are TWO parts of antifreeze in the place of perennial operation or partial operation:

Spray Water System and Internal Circulating Water System (softened water).

For the anti freezing problem of spray water system, an electric heater is usually added in the water pan, which is generally started when the spray water is lower than 5 ℃ and stops when the spray water is above 8 ℃.

The temperature probe transmits the signal to the control cabinet to automatically control the start and stop of the electric heater. The power selection of electric heater depends on circulating water volume and external air temperature.

2.Ethylene glycol solution or electric heating equipment can be added to prevent freezing of internal circulating water system.

The freezing point temperature of glycol solution should be selected below the local historical minimum temperature.

For the larger cooling system, we can consider digging a pool to put the spray water into it, which can save the power consumption due to electric heating operation.

Sự cố vận hành và biện pháp khắc phục của thiết bị lạnh trong mùa đông Đọc thêm »

So sánh giữa Van giãn nở điện tử và Van giãn nở nhiệt

So sánh giữa Van giãn nở điện tử và Van giãn nở nhiệt

Bây giờ ngày càng có nhiều thiết bị làm lạnh dân dụng và thương mại sử dụng van mở rộng điện tử để thay thế van mở rộng nhiệt ban đầu. Van mở rộng điện tử và van giãn nở nhiệt có cùng cách sử dụng cơ bản, nhưng khác nhau về hiệu suất.

1. Phạm vi điều chỉnh

At present, the regulating range of thermal expansion valve is generally narrow. The heat pump unit should not only refrigeration, but also heating, and the ambient temperature range of the suitable occasions is from15 ℃ to + 43 ℃, and the corresponding refrigerant evaporation temperature will work in the range of25 ℃5 ℃. In addition, if there are multiple compressors in the refrigeration circuit, the number of compressors in operation will change accordingly with the change of user load, resulting in dramatic change of refrigerant flow.

Do đó, một van giãn nở nhiệt duy nhất không có khả năng hoạt động của các đơn vị bơm nhiệt lớn. Hiện tại, nhiều sản phẩm bơm nhiệt quy mô lớn được thiết kế với vòng lặp đơn và máy nén đơn, và hệ thống van mở rộng có chế độ làm lạnh độc lập và chế độ sưởi ấm được áp dụng, sẽ làm tăng độ phức tạp và chi phí sản xuất của hệ thống. Van mở rộng điện tử có thể được điều chỉnh chính xác trong khoảng 15% ~ 100%.

Theo hiệu ứng sử dụng hiện tại, một van mở rộng điện tử duy nhất có thể đáp ứng quy định của bộ phận bơm nhiệt trong các điều kiện trên. Phạm vi điều chỉnh có thể được đặt theo đặc điểm của các sản phẩm khác nhau, làm tăng tính linh hoạt.

2. Kiểm soát quá nhiệt

(1) Điểm kiểm soát siêu nhiệt:

Đối với van giãn nở nhiệt, thường chỉ có thể điều khiển quá nhiệt ở ổ cắm thiết bị bay hơi. Trong hệ thống máy nén đã đóng và đóng hoàn toàn, điểm điều khiển có thể được đặt không chỉ tại ổ cắm thiết bị bay hơi, mà còn tại cổng hút máy nén, có thể điều khiển quá trình quá nhiệt của máy nén để đảm bảo hiệu quả của máy nén.

(2) Giá trị cài đặt siêu nhiệt:

Đối với van giãn nở nhiệt, giá trị cài đặt quá nhiệt của nó thường được đặt bởi nhà sản xuất trong quy trình sản xuất, thường là 5, 6 ℃ hoặc 8. Mức độ quá nhiệt của van mở rộng điện tử có thể được đặt thủ công theo các đặc tính khác nhau của sản phẩm. Ví dụ, quá nhiệt của đầu ra thiết bị bay hơi được đặt thành 6, và quá nhiệt của hút máy nén có thể được đặt thành 15, rất linh hoạt.

(3) Tính ổn định của kiểm soát quá nhiệt trong điều kiện hoạt động không chuẩn:

Các giá trị cài đặt siêu nhiệt của van giãn nở nhiệt đều được đặt trong các điều kiện tiêu chuẩn. Tuy nhiên, do các đặc điểm của việc sạc chất lỏng làm việc, khi hệ thống lệch khỏi điều kiện làm việc tiêu chuẩn, quá nhiệt sẽ lệch khỏi giá trị đã đặt với sự thay đổi áp suất ngưng tụ, điều này sẽ không chỉ gây ra sự giảm hiệu quả của hệ thống, mà còn gây ra sự dao động của hệ thống. Mức độ siêu nhiệt của van mở rộng điện tử được đặt bởi bộ điều khiển một cách giả tạo và mức độ siêu nhiệt thực tế của hệ thống được tính toán bởi các tham số của điểm điều khiển được thu thập bởi cảm biến, do đó không có vấn đề như vậy.

(4) Trí thông minh của quy định hệ thống:

Kiểm soát siêu nhiệt của van giãn nở nhiệt dựa trên trạng thái của điểm điều khiển hiện tại, được xác định bởi các đặc điểm của chất lỏng làm việc được lấp đầy. Nó không thể đánh giá xu hướng thay đổi của hệ thống. Logic điều khiển của van mở rộng điện tử có thể áp dụng các hệ thống điều khiển thông minh khác nhau theo đặc tính thiết kế và sản xuất của các sản phẩm khác nhau. Nó không chỉ có thể điều chỉnh trạng thái hiện tại của hệ thống, mà còn phân biệt các đặc điểm của hệ thống theo tốc độ thay đổi của mức độ quá nhiệt và các tham số khác. Các phương pháp điều khiển tương ứng được áp dụng cho các xu hướng thay đổi hệ thống khác nhau. Do đó, tốc độ phản ứng và sự phù hợp của nó đối với các thay đổi của hệ thống là vượt trội so với van giãn nở nhiệt.

3. Tốc độ phản ứng

Van giãn nở nhiệt được điều khiển bằng cách tận dụng các đặc tính nhiệt của môi trường làm việc làm đầy, do đó, các đặc tính mở và đóng của nó như sau:

(1) Độ nhạy của phản ứng và tốc độ mở và đóng chậm.

(2) Nói chung, tốc độ mở và đóng của van giãn nở nhiệt tương đối phù hợp.

(3) Trong quá trình khởi động đơn vị, có quá nhiệt tĩnh. Độ quá nhiệt (SH) của van giãn nở nhiệt bao gồm siêu nhiệt tĩnh (SS) và mở siêu nhiệt (HĐH). Do sự tồn tại của quá nhiệt tĩnh, sẽ có xu hướng trì hoãn việc mở van giãn nở nhiệt trong khi khởi động.

Chế độ lái của van tiết lưu điện tử là bộ điều khiển tính toán các thông số do cảm biến thu thập, gửi lệnh điều chỉnh đến bảng dẫn động, bảng dẫn động xuất tín hiệu điện đến van tiết lưu điện tử để điều khiển hoạt động của van tiết lưu điện tử. Chỉ mất vài giây để van tiết lưu điện tử chuyển từ trạng thái đóng hoàn toàn sang mở hoàn toàn. Nó có tốc độ phản ứng và hành động nhanh, không có hiện tượng quá nhiệt tĩnh. Hơn nữa, các đặc tính và tốc độ đóng mở có thể được thiết lập thủ công, đặc biệt phù hợp cho việc sử dụng các bộ phận bơm nhiệt có điều kiện làm việc biến động nghiêm trọng.

4. Sự đa dạng của các chức năng kiểm soát

Để ngăn chặn quá tải máy nén gây ra bởi áp suất và dòng chảy lạnh quá mức ở phía bay hơi trong quá trình khởi động ban đầu của thiết bị, van giãn nở nhiệt thường được trang bị chức năng MOP, nghĩa là van mở rộng chỉ có thể được mở khi áp suất bay thấp hơn giá trị đã đặt. Tuy nhiên, so với van mở rộng điện tử, chức năng của nó vẫn đơn điệu.

Cấu trúc của van tiết lưu điện tử có thể được coi là sự kết hợp hữu cơ giữa cơ cấu ga và van điện từ và có thể được điều chỉnh bằng bộ điều khiển. Do đó, theo các đặc tính khác nhau của sản phẩm, nó cho thấy sự đa dạng và ưu việt của chức năng điều khiển trong các điều kiện khởi động thiết bị, thay đổi tải, rã đông, tắt máy và bảo vệ lỗi. Ví dụ: van tiết lưu điện tử để điều chỉnh lưu lượng môi chất lạnh không chỉ có thể điều khiển thiết bị bay hơi mà còn có thể dùng để điều chỉnh bình ngưng.

Khi điều kiện bay hơi cho phép, nếu áp suất ngưng tụ quá cao, van giãn nở có thể được đóng đúng cách để giảm lưu lượng môi chất lạnh trong hệ thống và tải ngưng tụ, nhằm giảm áp suất ngưng tụ và nhận ra hoạt động hiệu quả và đáng tin cậy của thiết bị.

So sánh giữa Van giãn nở điện tử và Van giãn nở nhiệt Đọc thêm »

Trình tự vận hành máy làm lạnh nước

Trình tự vận hành máy làm lạnh nước

1. DANH SÁCH KIỂM TRA TRƯỚC KHI ĐIỆN VÀO

KHI cả nguồn điện và nguồn nước đều đáp ứng yêu cầu thì chúng ta có thể nhập nguồn: ĐẦU TIÊN, nhấn nút nguồn BẬT và kiểm tra:

① MỨC CHẤT LỎNG VÀ MỞ VAN BƠM:

Mức chất lỏng của bể nước lạnh có đáp ứng yêu cầu hay không và van trước và sau của bơm nước lạnh đã được mở hay chưa;

② MỞ THÁP NƯỚC VÀ BƠM NƯỚC

Bật công tắc của tháp nước làm mát và bơm nước làm mát, đồng thời chú ý đến việc mở van đầu vào và đầu ra của nước làm mát. (Lưu ý: loại làm mát bằng gió không cần tháp nước giải nhiệt)

③KIỂM TRA HƯỚNG QUAY

Khi đáp ứng tất cả các điều kiện trên, bạn có thể sử dụng chế độ nhích để kiểm tra xem hướng bơm nước làm mát, bơm nước lạnh, quạt tháp giải nhiệt và quạt ngưng tụ của bộ làm mát không khí có chính xác hay không và liệu truyền nước và hút không khí và xả là bình thường. Nếu không, chúng phải bị loại bỏ trước tiên.

2. NHẤN NÚT MỞ MÁY LÀM LẠNH VÀ ĐỂ NÓ CHẠY

Bật lại công tắc chạy của máy làm lạnh và máy bơm nước lạnh bắt đầu chạy. Xin lưu ý rằng van đầu vào và đầu ra của nước lạnh phải được mở và máy nén sẽ tự động chạy sau công tắc trễ. Vui lòng kiểm tra và điều chỉnh nhiệt độ cần thiết.

3. Sự khác biệt về trình tự khởi động của chiller giải nhiệt bằng nước và giải nhiệt bằng không khí:

① Bộ làm lạnh làm mát bằng nước:

bật quạt tháp giải nhiệt và bơm nước làm mát trước, sau đó bật máy làm lạnh

② Bộ làm lạnh làm mát bằng không khí:

có thể được bắt đầu trực tiếp

4. Trình tự tắt máy:

① Bộ phận làm mát bằng nước:

tắt máy làm lạnh trước, sau đó tắt quạt tháp giải nhiệt và bơm nước làm mát

② Bộ làm mát bằng không khí:

Nó có thể được tắt trực tiếp.

Trình tự vận hành máy làm lạnh nước Đọc thêm »

Industrial Water chiller installation

Yêu cầu lắp đặt máy làm lạnh nước công nghiệp

Installation Requirements of Industrial Water Chiller

All the Installation requirements of industrial water chiller you should notice to make sure the chilling unit can run as long as it can.

Industrial chillers can be divided into two categories according to the heat dissipation mode: 1. Water cooling units; 2. Air cooling units.

The water-cooled unit must be connected with the cooling tower and the inlet and outlet pipes of cooling water and chilled water. The cooling tower and cooling pump should be selected according to the refrigeration capacity and compression power, with the inlet pressure ≥ 1.5bar, and the diameter of the inlet and outlet pipe should be consistent with the diameter of the cooling water inlet and outlet pipe.

However, the air-cooled unit only needs to connect the chilled water inlet and outlet pipes and make-up water source. After the power supply is connected, the operation can be carried out. The ventilation should be smooth, and there should be no dust and debris around to avoid being inhaled into the unit.

1.The diameter of the water pipe

The diameter of the water pipe connection port reserved by the unit is standard size. When the remote transmission is adopted, a larger diameter water pipe must be used for connection. In any case, the diameter of the water pipe should not be smaller than the standard diameter of the connection port, otherwise, the pressure alarm will be given and the compressor and water pump will be damaged greatly.

2.Connecting The Water Pipe

When connecting the water pipe, the user should refer to the installation diagram to connect the pipeline, confirm the position of the inlet and outlet pipe, distinguish the cooling water pipe and the chilled water pipe.The wrong connection of the pipe will damage the unit.Only after ensuring the normal connection of the whole system can the system be started up and run.

3.With Connector or Flange

When the water pipe is connected to the unit, it must be connected with a connector or flange, so that it can be easily removed when necessary.

4.Connect a Hose

A section of hose is connected to the outlet and inlet of the water pipe to reduce vibration transmission.

5.Valves and Filter

If permitted, install valves on water pipes to effectively control water flow. It is suggested to install a filter at the water inlet to prevent sediment and debris.

6.Check Leakage Problem

Check the internal and external have leakage problem or not,when the water inlet/outlet valve of evaporator and condenser is fully opened.

7.Wrap With Insulation Material

The water pipe should be wrapped with enough insulation cotton to protect it from frost on the surface and keep the chilling water temperature.

8.Winter Protection Measures

In winter, when the unit stops operation, the water in the water pump and water pipe may freeze, causing damage to the unit and water pipe. In order to prevent icing, when the unit stops, the water pump can be effectively started. If there is still possibility of icing, all water in the water pipe will be discharged. If drainage is difficult, an anti icing mixture such as ethylene glycol or propanol can be used.

9.By-pass Pipe

When installing the unit, please install the bypass pipe in the chilled water pipeline device. When the chilled water outlet valve is turned down, the bypass pipe valve can be adjusted to relieve the pump pressure and prevent the evaporator from freezing.

10.Check Before Running

When the air-cooled chiller is started up and running, please pay attention to whether the water pump and exhaust fan turn normally before starting up and running.

11.High/Low Pressure

When the unit is running, please pay attention to the pressure display content: water cooled high pressure is (1.2 ~ 1.8MPa), low pressure is (0.3 ~ 0.6MPa); air cooled high pressure is (1.2 ~ 1.9mpa), low pressure is (0.3 ~ 0.6MPa). If the value is too high or too low, it means that the fault is a precursor or improper use. Please check it in time or inform the manufacturer to deal with it. Maintenance in advance is better than repair afterwards.

12.Cooling Water and Scale

To ensure that the condenser is not easy to scale and can be used for a long time, please use softened water (or tap water) as cooling water. If a cooling tower is used, the cooling water should be replaced regularly.

13.Regular Cleanning

The condenser and evaporator of the chiller usually need to be cleaned after a period of use (the cleaning cycle depends on the surrounding environment and water quality).

14.Temperature Setting

It is better to control the outlet water temperature of the unit at 7 ~ 12 ℃. When adjusting the temperature controller, please note that low temperature will cause some protection devices of the unit to fail.

15.Electric Control Elements and Protection Devices

All electric control elements and protection devices of the unit have been strictly tested by the manufacturer. Users are not allowed to change or remove them during inspection and maintenance. Forced operation without protection will cause great damage to the unit.

Yêu cầu lắp đặt máy làm lạnh nước công nghiệp Đọc thêm »

Đặc điểm và ưu điểm của các loại máy làm lạnh

Đặc điểm và ưu điểm của
các loại Máy làm lạnh nước

1.

Máy làm lạnh nước dạng hộp:

Nó có cấu trúc nhỏ gọn, có bình chứa nước và máy bơm nước bên trong. Nó phù hợp cho các thiết bị có đường ống bên ngoài kín.

Model làm mát bằng nước cần được trang bị bơm nước làm mát và tháp giải nhiệt trước khi đưa vào sử dụng.

2.

Máy làm lạnh làm mát bằng không khí kiểu hộp:

Ngoài tất cả công năng của loại hộp, không cần thêm bơm nước làm mát và tháp giải nhiệt.

Nó rất dễ dàng để cài đặt và vận hành. Nó phù hợp cho các thiết bị và xưởng sản xuất linh hoạt nhỏ, nơi lắp đặt tháp giải nhiệt vô điều kiện.

3.

Máy làm lạnh nước loại mở làm mát bằng nước:

Nó không được trang bị bể chứa nước lạnh và máy bơm nước, nhưng có thể kết nối với máy bơm nước và bể chứa nước theo yêu cầu.

Thể tích bể chứa nước và đầu bơm không bị giới hạn, có thể đáp ứng tốt hơn nhu cầu của các thiết bị công nghiệp khác nhau.

Cấu trúc mở, dễ dàng vệ sinh và bảo trì.

4.

Máy làm lạnh nhiệt độ thấp làm mát bằng nước hoặc làm mát bằng không khí:

Nên sử dụng dung dịch chống đông (ethylene glycol hoặc nước muối nhiệt độ thấp) làm chất làm lạnh mang và nhiệt độ đầu ra có thể dưới 0.

Nó bao gồm ba loạt: nhiệt độ cao (nhiệt độ đầu ra nước: 3oC – 5oC), nhiệt độ trung bình (nhiệt độ đầu ra nước: – 5oC – 10oC) và nhiệt độ thấp (nhiệt độ đầu ra nước – 15oC), có thể đáp ứng các yêu cầu nhiệt độ thấp của nhiều thiết bị khác nhau và cũng có thể được tùy chỉnh theo yêu cầu đặc biệt của khách hàng.

5.

Loại trục vít làm mát bằng nước:

Được sử dụng với thiết bị ngưng tụ vỏ và ống và thiết bị ngưng tụ vỏ và ống, có đặc điểm cấu trúc đơn giản, trao đổi nhiệt ổn định, hiệu quả lâu dài và bảo trì thuận tiện.

Thiết bị có các thiết bị bảo vệ an toàn đáng tin cậy, bao gồm: bộ bảo vệ điện áp cao và thấp, bộ bảo vệ quá nhiệt khí thải, bộ bảo vệ quá nhiệt động cơ máy nén, bộ bảo vệ dòng quá tải, bộ bảo vệ nhiệt độ chống đông, bộ bảo vệ dòng nước, công tắc dừng khẩn cấp, bu lông dễ nóng chảy nhạy cảm với nhiệt độ, van an toàn, v.v. .

Nó được công nhận là thành phần cấu trúc lý tưởng nhất của máy chủ làm lạnh trung tâm.

6.

Loại ống titan chống ăn mòn:

Thiết bị bay hơi titan đặc biệt có thể tránh ăn mòn chất lỏng axit và có thể đóng băng trực tiếp mạ điện, chất lỏng oxy hóa, nước biển, nước muối và các chất lỏng ăn mòn khác.

Đặc điểm và ưu điểm của các loại máy làm lạnh Đọc thêm »

Chuẩn bị trước khi lắp đặt máy làm lạnh nước

Find it hard or complicate to install a water chiller? Don’t know how to pick up a right place to settle your new water chiller?

Actually , you just need to do below steps one by one.Then everything will become very simple.

Let’s do it!

Check the components are complete

Before installation, check whether the components of the unit are complete.

The Right Cooling water tower and Cooling water pump

Select the appropriate cooling tower (air cooling type does not need cooling tower), and the capacity of cooling water pump should match the model. Please install according to the size of the body pipe, do not reduce the size of the cooling pipe, in order to avoid causing high pressure overload, affecting the cooling effect and increasing power consumption.

Correct handling methods

Correct handling method: use stacker, crane and drum. Do not drag the machine by force. Since the equipment has been debugged before leaving the factory, the system has pressure, so strong vibration is not allowed during loading and unloading, handling and installation. It is not allowed to invert, tilt or side set the unit during handling.

The right installation location requested:

The water chiller is an indoor device. If the user needs to place the equipment outdoors, it should be well protected from rain and sun, and should not be directly exposed to the outside.

 

The installation location should be a place with stable foundation, open surroundings, ventilation, avoiding corrosion and pollution, and convenient for installation and maintenance.

Since the unit itself will generate heat, it is necessary to avoid high temperature area around the unit during installation to meet the effective heat dissipation of the equipment, especially to ensure that the condenser of air-cooled chiller is well ventilated.

Avoid placing high-power inverter, welding machine and other equipment with interference sources near the equipment, and the installation space of the unit shall not be less than the size shown in the figure below. The figure shows the minimum installation space of the unit (unit: mm).

Water-cooled water chiller (Box type or Open type)
Air-cooled water chiller

The unit without caster at the bottom

The unit without caster at the bottom must be placed on the horizontal concrete base, and there must be no less than 3mm thick damping rubber pad between the unit and the concrete base

It is better to install large air-cooled units in outdoor space.

On the other hand, it can reduce heat emission. When placing, please support the bottom of the unit with bracket to make it ventilate smoothly and prevent rusting.

Note:

(1) the power load and grounding part shall be constructed in accordance with relevant laws and regulations

(2) The chilled water pipes of newly installed chillers must be covered with insulation layer.

Chuẩn bị trước khi lắp đặt máy làm lạnh nước Đọc thêm »

Ứng dụng của thiết bị làm lạnh công nghiệp APT

Ứng dụng công nghệ điện lạnh năm 2021

With the development of refrigeration industry, the application of refrigeration technology is becoming more and more extensive. Now it has penetrated into all fields of people’s life and production activities, from daily clothing, food, housing, transportation, to cutting-edge science and technology can not do without refrigeration technology.

1. Food Engineering

 

In order to prolong and improve the quality, economic life and value of perishable food, it is necessary to maintain a stable low temperature environment in the whole circulation process of perishable food from purchase or fishing, processing, storage, transportation to sales. This requires a variety of refrigeration facilities, such as cold processing equipment, refrigerated warehouses, refrigerated transport vehicles or ships, refrigerated sales counters and so on.

 

2. Air conditioning engineering

Air conditioning engineering is a wide application field of refrigeration technology. The temperature, humidity and cleanliness of the environment are required to be controlled in different degrees in optical instruments, precision measuring tools, textile workshops and computer rooms; comfortable air conditioning systems are also required for public buildings such as gymnasiums, great halls, hotels and other public buildings, cars, airplanes, and large buses.

3. Mechanical and electronic industry

Máy làm lạnh nước công nghiệp 20HP

 

Precision machine tool oil pressure system uses refrigeration to control the oil temperature, which can stabilize the oil film stiffness and make the machine work normally. Low temperature treatment of steel can improve the properties of steel, improve the hardness and strength of steel, and prolong the service life of workpiece. Multi channel communication, radar, satellite ground station and other electronic equipment also need to work in low temperature.

 

Swimming pool water chiller 1HP-3HP

Plasma, vaccines and some special drugs need to be preserved at low temperature. Low temperature anesthesia, low temperature surgery and cold compress cooling of patients with high fever also need refrigeration technology.

4. National defense industry and modern science

It is also necessary to simulate the performance

of these weapons and vehicles in the cold environment. Artificial rainfall also needs cooling.

Ứng dụng công nghệ điện lạnh năm 2021 Đọc thêm »